Journal of Agricultural Engineering

  • Year: 2003
  • Volume: 40
  • Issue: 1

Performance of Single Pass Earth-Tube Heat Exchanger: An Experimental Study

  • Author:
  • Girja Sharan1, Ratan Jadhav2
  • Total Page Count: 8
  • DOI:
  • Page Number: 1 to 8

1 Cummins-IIMA Lab, Centre for Mgt in Agriculture, Indian Institute of Management, Ahmedabad.

2 SEWA, Ahmedabad, Gujarat, India.

null

Abstract

A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating modes. ETHE consisted of 50 m mild steel pipe of 10 cm nominal diameter and 3 mm wall thickness, buried 2.85 m deep below ground. Ambient air was pumped through it for conditioning. Tests were conducted on three consecutive days in each month. The ETHE conditioned 5.6 m3/min of 40.6°C air to 26.6°C in cooling mode, and 8.3°C air to 23.0°C in heating mode. Average COP was 3.3 in cooling and 3.8 in heating mode.